Requirement of Overcurrent Protection

As per IS/IEC 62548, an overcurrent protection device (or a DC Fuse) is required in a system, if the below mentioned condition is true:

[(Ns – 1) x Isc_mod] > [Imod_max_ocpr]

Where,

Ns = Number of strings connected in parallel (To be determined from design considerations)

Isc = Short Circuit Current of Solar PV Modules at STC (To be determined from Datasheet)

Imod_max_ocpr = Max Series Fuse Rating (To be determined from Datasheet)

Sizing of solar DC fuse

As per IS/IEC 62548, current rating of an overcurrent protection device (or a DC Fuse) should be calculated as:

In > 1.5 x Isc_mod

In < 2.4 x Isc_mod

In <= Imod_max_ocpr

Where,

In = Current rating of DC Fuse

Isc = Short Circuit Current of Solar PV Modules at STC (To be determined from Datasheet)

Imod_max_ocpr = Max Series Fuse Rating (To be determined from Datasheet)

Voltage rating of a DC Fuse should be equal to or more than the string maximum voltage


0 Comments

Leave a Reply

Your email address will not be published. Required fields are marked *

Let's Get Connected